Last time I had an HVAC issue, I got tons of help from here. Well, another issue has reared its head and I'm asking for help once again
I'm having an ignition issue with my gas furnace. Inducer fan kicks on, pressure switch hose / nipple isn't clogged, igniter glows (new igniter, just replaced it), than turns off. Igniters glows a total of 3 times, than system goes into lockout mode. Control board has a LED error code of one flash. Meaning ignition failure (manual says to check gas flow, gas pressure, gas valve, and flame sensor)
I sanded the flame sensor, it was slightly carbonized, but not terrible looking. Replaced it, issue still occurs.
Gas flow is turned on, I haven't messed with gas pressure, as it worked fine before.
Any testing I can do with the gas valve? I ordered a replacement flame sensor just in case. They're a good replacement to have around anyway I hear.
Oh, also testing voltage to the flame sensor, and it appears to not be an issue.
Any other ideas / things I can test before calling for service?
I'm having an ignition issue with my gas furnace. Inducer fan kicks on, pressure switch hose / nipple isn't clogged, igniter glows (new igniter, just replaced it), than turns off. Igniters glows a total of 3 times, than system goes into lockout mode. Control board has a LED error code of one flash. Meaning ignition failure (manual says to check gas flow, gas pressure, gas valve, and flame sensor)
I sanded the flame sensor, it was slightly carbonized, but not terrible looking. Replaced it, issue still occurs.
Gas flow is turned on, I haven't messed with gas pressure, as it worked fine before.
Any testing I can do with the gas valve? I ordered a replacement flame sensor just in case. They're a good replacement to have around anyway I hear.
Oh, also testing voltage to the flame sensor, and it appears to not be an issue.
Any other ideas / things I can test before calling for service?